Product photo
Industrial UPS 5-7.5kVA
XMI-D Series · Industrial UPS for electrical power systems (5kVA / 7.5kVA) with 0ms transfer and static bypass support.
Model: XMI50D(R/P) / XMI75D(R/P)
Capacity
5kVA / 7.5kVA
Power factor
0.8
Input
220Vac · 165–275Vac range · 50±5%Hz · Rated DC: 110/220Vdc
Output
Single phase 220Vac (±1%) · 50±0.5%Hz · THDu <3% linear / <5% non-linear · 0ms transfer
| Parameter | Value |
|---|---|
| Series | XMI-D |
| Applicable models (this page) | XMI50D(R/P) (5kVA) · XMI75D(R/P) (7.5kVA) |
| Capacity | 5kVA / 7.5kVA |
| Rated input voltage | 220Vac |
| Input voltage range | Phase voltage (165 ~ 275) Vac |
| Input frequency range | (50 ± 5%)Hz |
| Rated DC voltage | 110/220Vdc |
| Rated output voltage | Single phase 220Vac |
| Output voltage accuracy | (220 ± 1%)Vac |
| Output frequency | (50 ± 0.5%)Hz |
| Output power factor | 0.8 |
| THDu | <3% (linear full load) · <5% (non-linear full load) |
| Overload capacity | 105%–125%: switch to bypass in 10 min · 125%–150%: switch to bypass in 1 min · >150%: immediately switch to bypass |
| Switching time | 0ms |
| Parallel operation current imbalance | ≤5% |
| Protection (overload) | Switch to bypass power supply; automatically switch to mains power after load reduction |
| Protection (overheat) | >85℃: switch to bypass power supply |
| Protection (short circuit) | Inverter shutdown with protection alarm |
| Protection (fault) | Switch to bypass with protection alarm |
| Protection (undervoltage) | Automatic shutdown |
| LED indication | AC power · inverter · bypass · DC undervoltage · overload · fault |
| LCD display | AC in/out V & Hz · DC input V · load % · apparent/active power · output current · UPS status |
| Alarm | Input abnormality · low battery voltage · overload · other error |
| Communication | RS-232/RS485 (Modbus) · dry contact · SNMP remote monitoring (optional) |
| Operating temperature | (-5 ~ 40)℃ |
| Relative humidity | 0–95% (no condensation) |
| Noise | <55dB @ 1 meter |
| Mechanical | Rack-mount with transformer (internal or external transformer options depending on configuration) |
| Minimum order | 85 |